Electrical Distribution Boxes Daily Price 3 Day Price
Electrical spider distribution box rental Spider Distribution Box $30 Call

Recommended Wire Gauges

Maximum Current Load in Amperes Gauge of Copper Conductor Maximum Cord Length with 5% Voltage Drop Typical Service Length Approx. % Voltage Drop for Typical Service Length
7 18 65 ft. 100 ft. ( 9% )
10 16 71 ft. 100 ft. ( 6% )
15 14 75 ft. 125 ft. ( 8% )
20 12 90 ft. 125 ft. ( 6% )
25 10 115 ft. 150 ft. ( 6% )
35 8 130 ft. 150 ft. ( 5% )
45 6 158 ft. 200 ft. ( 6% )
60 4 188 ft. 200 ft. ( 5% )